        Old 19-05-2020, 11:26 AM   #4531
        Senior Member
         
        Join Date: Oct 2003
        Posts: 652
        Mine is the old hdb without the Aircon ledge. There is no breaker near the compressor.
        Oh... Then, it's hard to troubleshoot.
        If all 3 FCU have no power, it's very likely that there is no power to the outdoor unit[compressor].
        A few years back, I encountered same issue. No power at my all 3 FCU.
        My aircon installer used very small wire[same as those to FCU] for compressor and the wire burnt out/broken.
        I ended up replacing them with 2 bigger ones.
        bumperbee likes this.
        mkaung2000 is online now   Reply With Quote
        Old 19-05-2020, 11:49 AM   #4532
        Master Member
         
        Join Date: Aug 2000
        Posts: 4,078
        Oh... Then, it's hard to troubleshoot.
        If all 3 FCU have no power, it's very likely that there is no power to the outdoor unit[compressor].
        A few years back, I encountered same issue. No power at my all 3 FCU.
        My aircon installer used very small wire[same as those to FCU] for compressor and the wire burnt out/broken.
        I ended up replacing them with 2 bigger ones.
        Thanks. So any Aircon serviceman to recommend me or should I call mitsubishi to repair?
        android is offline   Reply With Quote
        Old 19-05-2020, 01:40 PM   #4533
        Junior Member
         
        Join Date: Apr 2020
        Posts: 8
        Hi, i am a senior citizen and would like to ask for everyone kind advise here. Currently my 4rm have only 1 single split installed in the master bedroom. My 2 other rooms don't have aircon because my 2 children don't like to use aircon. But because of the circuit breaker, they work from home now but in the afternoon it get quite hot because of direct afternoon sun. Because this Covic 19 my company closed and I lost my job so on tight budget. I am think to install a window aircon at the small square window lourve on the wall but the aircon shop owner say hdb not approved. Can anyone advise if the window unit be installed on top of the sliding window? Thanks

        Last edited by macdonalds109; 19-05-2020 at 01:43 PM..
        macdonalds109 is offline   Reply With Quote
        Old 19-05-2020, 04:22 PM   #4534
        Senior Member
         
        blade39's Avatar
         
        Join Date: Sep 2010
        Posts: 2,403
        Hi all,

        Aircon split type 3 system.

        Symptom as follow.

        Two problem units not responding to remote and to physical button press.

        Work around is to turn off the breaker for around 15min and turn on breaker again. They will response and work OK.
        If 3 to 4 days no turn them on. They will be "dead" again.

        Have been using this work around to keep them going, untill this week where they completely don't response. Seem really spoil.

        Anyone has the same issue previously and got it repaired? Get recommend the service person?

        Is it indoor unit PCB board uplorry?

        Sent from Xiaomi POCOPHONE F1 using GAGT
        blade39 is offline   Reply With Quote
        Old 19-05-2020, 09:23 PM   #4535
        Member
         
        Join Date: Jun 2004
        Posts: 258
        Thanks. So any Aircon serviceman to recommend me or should I call mitsubishi to repair?
        Any aircon vendor can do it
        craigchua is offline   Reply With Quote
        Old 19-05-2020, 09:23 PM   #4536
        High Supremacy Member
         
        MikeDirnt78's Avatar
         
        Join Date: Jun 2002
        Posts: 26,841
        Hi, i am a senior citizen and would like to ask for everyone kind advise here. Currently my 4rm have only 1 single split installed in the master bedroom. My 2 other rooms don't have aircon because my 2 children don't like to use aircon. But because of the circuit breaker, they work from home now but in the afternoon it get quite hot because of direct afternoon sun. Because this Covic 19 my company closed and I lost my job so on tight budget. I am think to install a window aircon at the small square window lourve on the wall but the aircon shop owner say hdb not approved. Can anyone advise if the window unit be installed on top of the sliding window? Thanks
        I doubt you can install on top of the sliding window. It poses a safety hazard without the proper bracket.

        Probably just get a 2nd hand aircon from carousell? They can supply and install.

        Alternatively and worst case scenario, just buy a portable aircon.
        bumperbee likes this.
        __________________
        Eat | Live | Punk Rock | Save | Invest | Finance | Fitness | Pixel | Tech | DIY
        POHA Cap. 256A
        MikeDirnt78 is offline   Reply With Quote
        Old 19-05-2020, 09:26 PM   #4537
        High Supremacy Member
         
        MikeDirnt78's Avatar
         
        Join Date: Jun 2002
        Posts: 26,841
        Thanks. So any Aircon serviceman to recommend me or should I call mitsubishi to repair?
        I suggest you engage a local and experience technician. Someone who dares to troubleshoot to components level.

        Don't engage from aircon contractors. These technicians don't deal with components level.

        They will probably suggest to buy a new one.
        bumperbee likes this.
        __________________
        Eat | Live | Punk Rock | Save | Invest | Finance | Fitness | Pixel | Tech | DIY
        POHA Cap. 256A
        MikeDirnt78 is offline   Reply With Quote
        Old 20-05-2020, 11:45 AM   #4538
        Senior Member
         
        Join Date: May 2018
        Posts: 523
        Hi all,

        Aircon split type 3 system.

        Symptom as follow.

        Two problem units not responding to remote and to physical button press.

        Work around is to turn off the breaker for around 15min and turn on breaker again. They will response and work OK.
        If 3 to 4 days no turn them on. They will be "dead" again.

        Have been using this work around to keep them going, untill this week where they completely don't response. Seem really spoil.

        Anyone has the same issue previously and got it repaired? Get recommend the service person?

        Is it indoor unit PCB board uplorry?

        Sent from Xiaomi POCOPHONE F1 using GAGT
        I have a similar issue with my system 2 just last week.

        Suggest you open up the electrical panel to see if there is blue wire burned inside.
        The aircon circuit breaker will not trip when the blue or neutral wire is burned due to some abnormality of the aircon so reset it make no difference

        I open up the electrical panel and found the aircon blue wire burned, remove the burn part and put back into the original terminal.
        Turn on aircon circuit breaker and the system works and running for the past week.
        I also open up the electrical box of outdoor unit and 2 FCU and find all the cables in good condition.

        No idea what is the real cause though
        simnonsg is offline   Reply With Quote
        Old 20-05-2020, 11:52 AM   #4539
        Senior Member
         
        Join Date: May 2018
        Posts: 523
        I check the circuit breaker in the living room. There is no trip. There was also no cut in power supply for the other appliances
        Suggest you open the electrical panel to check if neutral wire of aircon burned.
        If burned, do cut burned part and strip a portion of the wire and insert back to terminal, then turn on circuit breaker to see if it works.

        Also check the main switch of the aircon system to see if neutral wire is burned.
        bumperbee likes this.
        simnonsg is offline   Reply With Quote
        Old 20-05-2020, 04:55 PM   #4540
        Senior Member
         
        blade39's Avatar
         
        Join Date: Sep 2010
        Posts: 2,403
        I have a similar issue with my system 2 just last week.

        Suggest you open up the electrical panel to see if there is blue wire burned inside.
        The aircon circuit breaker will not trip when the blue or neutral wire is burned due to some abnormality of the aircon so reset it make no difference

        I open up the electrical panel and found the aircon blue wire burned, remove the burn part and put back into the original terminal.
        Turn on aircon circuit breaker and the system works and running for the past week.
        I also open up the electrical box of outdoor unit and 2 FCU and find all the cables in good condition.

        No idea what is the real cause though
        Electrical panel of indoor aircon unit?

        Sent from Xiaomi POCOPHONE F1 using GAGT
        blade39 is offline   Reply With Quote
        Old 20-05-2020, 06:12 PM   #4541
        Arch-Supremacy Member
         
        stupidog's Avatar
         
        Join Date: Feb 2005
        Posts: 12,022
        guys, recently my MBR aircon unit got this noise whenever i turn it on.

        sounds like a storm is coming from the unit lol

        can u pls listen to it and see what is going on ?

        Thanks in advance

        https://soundcloud.com/stupidog-sg/a.../s-Jd7S7mjK0zZ
        stupidog is offline   Reply With Quote
        Old 20-05-2020, 06:25 PM   #4542
        Member
         
        Join Date: Jun 2005
        Posts: 296
        Replacing my Aircon

        Hi,


        I wish to replace my closed to 20 years Starmex system 4.



        1) Which aircon model is recommended now? Still Starmex from Mitsubishi Heavy Industry?

        2) Where shall I go for purchase and install?
        3) I should also change the pipes?
        4) If I wish to change the location of 1 outlet, they will need to raise request for HDB for approval? And how much will it cost?



        Regards.
        ComputerTime is offline   Reply With Quote
        Old 20-05-2020, 07:13 PM   #4543
        Moderator
         
        petetherock's Avatar
         
        Join Date: Jan 2007
        Posts: 7,181
        Starmex is different from MHI.
        You should replace everything.
        I used a private contractor, but Gain City has been mentioned a few times, so that's a good place to begin for a HDB solution.
        bumperbee likes this.
        __________________
        POST YOUR QUESTIONS INSTEAD OF SENDING A PM



        Use the Search Button and Read the Stickies!




        My home theatre gear and my blog:

        https://peteswrite.blogspot.com/2020...tup-22020.html
        petetherock is offline   Reply With Quote
        Old 20-05-2020, 07:44 PM   #4544
        Senior Member
         
        Join Date: May 2018
        Posts: 523
        Electrical panel of indoor aircon unit?

        Sent from Xiaomi POCOPHONE F1 using GAGT
        Your home electrical panel where all the power circuit breakers is

        There is a circuit breaker label as AC for aircon and a blue wire label for AC
        inside the home electrical panel.
        simnonsg is offline   Reply With Quote
        Old 20-05-2020, 08:35 PM   #4545
        Master Member
         
        Join Date: Aug 2000
        Posts: 4,078
        Suggest you open the electrical panel to check if neutral wire of aircon burned.
        If burned, do cut burned part and strip a portion of the wire and insert back to terminal, then turn on circuit breaker to see if it works.

        Also check the main switch of the aircon system to see if neutral wire is burned.
        Hi, may I know the location of this electrical panel that you are refering to?
        android is offline   Reply With Quote